產(chǎn)品中心
Product Center當(dāng)前位置:首頁產(chǎn)品中心國產(chǎn)-耐壓絕緣接地泄漏低電阻儀國產(chǎn)-絕緣電阻測試儀ZC-7絕緣電阻表(兆歐表)ZC-7搖表
ZC-7型絕緣電阻表適用于測量各種變壓器絕緣電阻、電機(jī)絕緣電阻、電纜絕緣電阻、電氣設(shè)備及絕緣材料的絕緣電阻。
規(guī)格如下:
準(zhǔn)確度%(10.0)20.0基準(zhǔn)值為指示值,相當(dāng)于原1.0
100V/100MΩ,
100V/200MΩ,
100V/500MΩ
250V/250MΩ,
250V/500MΩ,
250V/1000MΩ
500V/500MΩ,
500V/1000MΩ,
500V/2000MΩ
1000V/1000MΩ,
1000V/2000MΩ,
1000V/5000MΩ
準(zhǔn)確度%(20.0)50.0相當(dāng)于原1.5
2500V/2500MΩ,
2500V/5000MΩ,
2500V/10000MΩ
5000V/5000MΩ,
5000V/10000MΩ.
規(guī)格額定電壓 | 測量上限(MΩ) | 有效測量范圍的準(zhǔn)確度等級 | 備注 | ||
100V | 200 | 0.5-20 | ⑸ | ⑽ |
|
100 | 0.5-20 | ||||
250V | 500 | 1-50 | ⑸ | ⑽ |
|
250 | 0.5-20 | ||||
500V | 1000 | 2-100 | ⑸ | ⑽ | 起始為1MΩ |
1000 | 2-100 | ||||
500 | 1-50 | ||||
1000V | 2000 | 5-200 | ⑸ | ⑽ | 起始為2MΩ |
2000 | 5-200 | ||||
1000 | 2-100 | ||||
2500V | 5000 | 10-500 | ⑽ | ⒇ | 起始為5MΩ |
5000 | 10-500 | ||||
2500 | 5-200 | ||||
5000V | 5000 | 50-2000 | ⑽ | ⒇ | - |
10000 | 50-2000 | ||||
20000 | 50-2000 |
1.ZC-7型絕緣電阻表的各項(xiàng)性能符合GB7676-1998(直接作用模擬指示電測量儀表用其附件)的技術(shù)要求及ZBN21012(絕緣電阻表)技術(shù)要求.
2.儀表的基準(zhǔn)值為指示值.
3.儀表的基本誤差以基準(zhǔn)值的百分?jǐn)?shù)表示,基本誤差的極限值不大于相應(yīng)準(zhǔn)確度的等級值。
0及 ∞刻度以標(biāo)尺長度的百分?jǐn)?shù)表示,其極限不大于標(biāo)尺全長的1%。
3.儀表端鈕開路電壓與額定電壓之差不大于額定電壓的10%
4.儀表端鈕開路電壓的峰值與有效值之比不大于1.5
5.儀表測量端鈕接如中值電阻時(shí)其中電壓與額定電壓之差不大于額定值的10%
6.儀表線路與外殼間的絕緣電阻不低于30MΩ
7.儀表線路與外殼間的絕緣電壓試驗(yàn)?zāi)苣褪?0Hz交流電壓,歷時(shí)1min的試驗(yàn).其試驗(yàn)見下表:
額定電壓 | 試驗(yàn)電壓(有效值) |
500V | 1 |
1000V | 1.5 |
2500V | 3.5 |
5000V | 5.4 |
8. 儀表發(fā)電機(jī)搖把額定轉(zhuǎn)速每分鐘120轉(zhuǎn)
9. 儀表自工作位置向任意方向傾斜時(shí),其指示值變化不大于基本誤差的二分之一
10.儀表的工作環(huán)境溫度對標(biāo)準(zhǔn)溫度(23°C)每變化10°C,由此引起指示改變不大于基本誤差
11.當(dāng)標(biāo)準(zhǔn)環(huán)境濕度自40-60%變化,由此引起指示值的改變不大于基準(zhǔn)值的1.5%
12.儀表的可靠性符合JB/T6214-1992《儀器儀表可靠性驗(yàn)證試驗(yàn)及測定試驗(yàn)指數(shù)分布導(dǎo)測》
13.儀表的運(yùn)輸貯存符合JB/T9329-1999《儀器儀表運(yùn)輸 運(yùn)輸貯存基本環(huán)境條件及實(shí)驗(yàn)方法》